According to the content of the "Technical Specifications for Fire Water Supply and Fire Hydrant Systems", today the editor will tell you about the installation requirements of the fire pump control cabinet.
The fire control room or duty room should have the following control and display functions. The fire control cabinet or control panel should be equipped with a manual direct pump start button connected through a special line.
The fire pump control cabinet or control panel should display the operating status of the fire water pump and pressure stabilizing pump, and should be able to display high and low water level warning signals as well as normal water levels of fire pools, high-level fire water tanks and other water sources.
When the fire pump control cabinet is installed in a dedicated fire pump control room, its protection level shall not be lower than IP30. When installed in the same space as a fire water pump, its protection level shall not be lower than IP55.
The fire pump control cabinet should be equipped with a mechanical emergency pump starting function, and it should be ensured that if a fault occurs in the control loop in the control cabinet, the fire pump will be started by a person with management authority. When the machinery is started in an emergency, the fire pump should be ensured to work normally within 5.0 minutes.